  "spec": "fio",
  "spec_version": "0.3.0",
  "capabilities": {
    "profile": "full-v0"
  },
  "manifest": {
    "id": "lbnl-power-chain-v2-5",
    "name": "LBNL Electrical Power Chain Tool",
    "description": "LBNL Electrical Power Chain Tool with version-pinned publisher workbook calculations, scenario inputs and formula-level audit traces.",
    "workbook": {
      "uri": "lbnl-power-chain-v2-5.xlsx",
      "locale": "en-US",
      "date_system": 1900
    }
  },
  "ports": [
    {
      "id": "transformer_input_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C16"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average input power of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 650.",
      "default": 650,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "transformer_output_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C17"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average output power of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 620.",
      "default": 620,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "transformer_capacity_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C18"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the nominal load capacity of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 850.",
      "default": 850,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "ups_input_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C19"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average input power of the UPS system in kW? Zero activates claimed-efficiency fallback; savings formulas still use measured input minus output, so supply measured input for retrofit analysis. Units: kW. Omitted input retains publisher's source default 580.",
      "default": 580,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "ups_output_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C20"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average output power of the UPS system in kW? Units: kW. Omitted input retains publisher's source default 500.",
      "default": 500,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "ups_capacity_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C21"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the total load capacity of all active UPS modules in kW? Units: kW. Omitted input retains publisher's source default 750.",
      "default": 750,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "ups_claimed_efficiency",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C22"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the UPS manufacturer's claimed efficiency at the calculated load factor shown at right? Used only when ups_input_kw is zero. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0,
        "max": 1
      }
    },
    {
      "id": "pdu_input_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C23"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average total PDU input power in kW? Units: kW. Omitted input retains publisher's source default 525.",
      "default": 525,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "pdu_output_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C24"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average total PDU output power in kW? Units: kW. Omitted input retains publisher's source default 500.",
      "default": 500,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "pdu_capacity_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C25"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the total load capacity of all active PDUs in kW? Units: kW. Omitted input retains publisher's source default 600.",
      "default": 600,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "generator_heater_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C26"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average backup generator engine block heater power demand in kW? Units: kW. Omitted input retains publisher's source default 10.",
      "default": 10,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "floor_area_sqft",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C27"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the data center floor area in sq. ft.? Units: ft². Omitted input retains publisher's source default 10000.",
      "default": 10000,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "it_equipment_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C28"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average IT equipment power demand in kW? Units: kW. Omitted input retains publisher's source default 515.",
      "default": 515,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "lighting_kw",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C29"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average lighting power demand in kW for the data center? Units: kW. Omitted input retains publisher's source default 20.",
      "default": 20,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "electricity_cents_per_kwh",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!C30"
      },
      "schema": {
        "type": "number"
      },
      "description": "What is the annual average unit cost of electricity in ¢/kWh? Units: cents/kWh. Omitted input retains publisher's source default 15.",
      "default": 15,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "building_power_factor",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C16"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the building power factor?  Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "<0.9",
          "≥0.9",
          "Do not know."
        ]
      }
    },
    {
      "id": "building_thd",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C17"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the building total harmonic current distortion (THD) at main feeder panel? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          ">5%",
          "≤5%",
          "Do not know."
        ]
      }
    },
    {
      "id": "phase_balance",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C18"
      },
      "schema": {
        "type": "string"
      },
      "description": "Are the loads balanced between all phases for the transformers, UPSs, and PDUs? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Out of balance by more than 10%.",
          "Balanced to within 10% or less.",
          "Do not know."
        ]
      }
    },
    {
      "id": "transformer_type",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C19"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the age and type of the main transformer serving the IT power chain? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Temp rise ≥150 C and age >15 years old.",
          "Temp rise ≥150 C and age ≤15 years old.",
          "Temp rise < 150 C and age ≥ 15 years old.",
          "Temp rise < 150 C and age < 15 years old.",
          "N/A (no main IT transformer).",
          "Do not know."
        ]
      }
    },
    {
      "id": "active_ups",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C20"
      },
      "schema": {
        "type": "string"
      },
      "description": "Is there an active UPS? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Yes.\".",
      "default": "Yes.",
      "constraints": {
        "enum": [
          "Yes.",
          "No.",
          "Do not know."
        ]
      }
    },
    {
      "id": "ups_eco_mode",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C24"
      },
      "schema": {
        "type": "string"
      },
      "description": "Is the UPS operating in eco-mode? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Yes.",
          "No.",
          "N/A (No UPS, or no eco-mode capability).",
          "Do not know."
        ]
      }
    },
    {
      "id": "ups_old_capacitors",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C25"
      },
      "schema": {
        "type": "string"
      },
      "description": "Are the UPS DC capacitors >5 years old? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Yes.",
          "No.",
          "Do not know.",
          "N/A (no UPS)."
        ]
      }
    },
    {
      "id": "noncritical_power_source",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C26"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the power source for non-critical loads? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "UPS.",
          "Utility power.",
          "Do not know."
        ]
      }
    },
    {
      "id": "pdu_transformer_type",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C27"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the age and type of the transformers in the PDUs? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Temp rise ≥150 C and age >15 years old.",
          "Temp rise ≥150 C and age ≤15 years old.",
          "Temp rise < 150 C and age ≥ 15 years old.",
          "Temp rise < 150 C and age < 15 years old.",
          "N/A (no transformers in PDUs).",
          "Do not know."
        ]
      }
    },
    {
      "id": "pdu_load_factor",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C28"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the average load factor for the active PDUs that contain transformers? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "<25%",
          "≥25-50%",
          ">50%",
          "Do not know."
        ]
      }
    },
    {
      "id": "it_power_factor",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C29"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the IT equipment power factor? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "<0.9",
          "≥0.9",
          "Do not know."
        ]
      }
    },
    {
      "id": "rack_power_source",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C30"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the power source for the IT racks? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Alternating current (AC).",
          "Direct current (DC).",
          "Do not know."
        ]
      }
    },
    {
      "id": "heater_power_source",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C31"
      },
      "schema": {
        "type": "string"
      },
      "description": "What is the power source for the emergency generator block heater(s)? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Utility power.",
          "Alternate power source, e.g. solar.",
          "Do not know."
        ]
      }
    },
    {
      "id": "heater_thermostat",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C32"
      },
      "schema": {
        "type": "string"
      },
      "description": "Does the block heater(s)/heater water jacket for emergency generator(s) operate with thermostat control? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "No.",
          "Yes.",
          "Do not know."
        ]
      }
    },
    {
      "id": "lighting_design",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C33"
      },
      "schema": {
        "type": "string"
      },
      "description": "Is the data center lighting well-designed? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "No, the data center is over-lit and/or light is provided where it is not needed.",
          "Yes, sufficient light is provided only to the areas that need it.",
          "Do not know."
        ]
      }
    },
    {
      "id": "lighting_control",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C35"
      },
      "schema": {
        "type": "string"
      },
      "description": "How are the lights controlled in the data center? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"No control (always on).\".",
      "default": "No control (always on).",
      "constraints": {
        "enum": [
          "No control (always on).",
          "Timeclock.",
          "Manual Control.",
          "Occupancy Sensor.",
          "Do not know."
        ]
      }
    },
    {
      "id": "lamp_type",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!C38"
      },
      "schema": {
        "type": "string"
      },
      "description": "What type of lamps are installed in the data center? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".",
      "default": "Do not know.",
      "constraints": {
        "enum": [
          "Compact Fluorescent (CFL) or T12 Fluorescent.",
          "T8 Fluorescent.",
          "T5 Fluorescent.",
          "LED.",
          "Do not know."
        ]
      }
    },
    {
      "id": "pursue_action_16",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H16"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 16; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_17",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H17"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 17; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_18",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H18"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 18; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_19",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H19"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 19; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_20",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H20"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 20; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".",
      "default": "No",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_21",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H21"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 21; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".",
      "default": "Yes",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_22",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H22"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 22; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".",
      "default": "Yes",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_23",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H23"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 23; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".",
      "default": "No",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_24",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H24"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 24; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_25",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H25"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 25; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_26",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H26"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 26; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_27",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H27"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 27; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_28",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H28"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 28; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_29",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H29"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 29; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_30",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H30"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 30; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_31",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H31"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 31; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_32",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H32"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 32; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_33",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H33"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 33; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_34",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H34"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 34; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_35",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H35"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 35; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".",
      "default": "No",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_36",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H36"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 36; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".",
      "default": "No",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_37",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H37"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 37; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".",
      "default": "Yes",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_38",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H38"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 38; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_39",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H39"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 39; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "pursue_action_40",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs B'!H40"
      },
      "schema": {
        "type": "string"
      },
      "description": "Pursue displayed action at row 40; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".",
      "default": "N/A",
      "constraints": {
        "enum": [
          "Yes",
          "No",
          "N/A"
        ]
      }
    },
    {
      "id": "new_ups_load_factor",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!E18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Post-retrofit UPS load fraction. Active if any UPS row 20–23 action is pursued; exact tenth-step lookup, no interpolation. Units: decimal fraction. Omitted input retains publisher's source default 0.8.",
      "default": 0.8,
      "constraints": {
        "enum": [
          0.1,
          0.2,
          0.3,
          0.4,
          0.5,
          0.6,
          0.7,
          0.8,
          0.9,
          1
        ]
      }
    },
    {
      "id": "new_pdu_load_factor",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!E26"
      },
      "schema": {
        "type": "string"
      },
      "description": "Post-action PDU loading; active with PDU rightsizing action. Units: source enum. Omitted input retains publisher's source default \">50%\".",
      "default": ">50%",
      "constraints": {
        "enum": [
          "<25%",
          "≥25-50%",
          ">50%"
        ]
      }
    },
    {
      "id": "implementation_cost_14",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J14"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 14. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_15",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J15"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 15. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_16",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J16"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 16. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_17",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J17"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 17. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_18",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 18. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 300000.",
      "default": 300000,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_22",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J22"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 22. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_23",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J23"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 23. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_24",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J24"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 24. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_25",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J25"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 25. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_26",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J26"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 26. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_27",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J27"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 27. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_28",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J28"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 28. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_29",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J29"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 29. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_30",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J30"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 30. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_31",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J31"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 31. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_33",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J33"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 33. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 15000.",
      "default": 15000,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "implementation_cost_36",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Action Results'!J36"
      },
      "schema": {
        "type": "number"
      },
      "description": "Estimated cost for action group row 36. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.",
      "default": 0,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "ups_savings_cap",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!D9"
      },
      "schema": {
        "type": "number"
      },
      "description": "Maximum combined savings fraction of UPS losses; source omits interactive effects. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.8.",
      "default": 0.8,
      "constraints": {
        "min": 0,
        "max": 1
      }
    },
    {
      "id": "lighting_savings_cap",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!D10"
      },
      "schema": {
        "type": "number"
      },
      "description": "Maximum combined savings fraction of lighting consumption. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.8.",
      "default": 0.8,
      "constraints": {
        "min": 0,
        "max": 1
      }
    },
    {
      "id": "emissions_region_index",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!T9"
      },
      "schema": {
        "type": "number"
      },
      "description": "Source list-box linked row: 1=Custom, 2..51 follows P11:P60 state abbreviations. The visible F20 text is not the formula selector. State map: 1=Custom, 2=AL, 3=AK, 4=AZ, 5=AR, 6=CA, 7=CO, 8=CT, 9=DE, 10=FL, 11=GA, 12=HI, 13=ID, 14=IL, 15=IN, 16=IA, 17=KS, 18=KY, 19=LA, 20=ME, 21=MD, 22=MA, 23=MI, 24=MN, 25=MS, 26=MO, 27=MT, 28=NE, 29=NV, 30=NH, 31=NJ, 32=NM, 33=NY, 34=NC, 35=ND, 36=OH, 37=OK, 38=OR, 39=PA, 40=RI, 41=SC, 42=SD, 43=TN, 44=TX, 45=UT, 46=VT, 47=VA, 48=WA, 49=WV, 50=WI, 51=WY Units: integer lookup index. Omitted input retains publisher's source default 1.",
      "default": 1,
      "constraints": {
        "enum": [
          1,
          2,
          3,
          4,
          5,
          6,
          7,
          8,
          9,
          10,
          11,
          12,
          13,
          14,
          15,
          16,
          17,
          18,
          19,
          20,
          21,
          22,
          23,
          24,
          25,
          26,
          27,
          28,
          29,
          30,
          31,
          32,
          33,
          34,
          35,
          36,
          37,
          38,
          39,
          40,
          41,
          42,
          43,
          44,
          45,
          46,
          47,
          48,
          49,
          50,
          51
        ]
      }
    },
    {
      "id": "custom_emissions_lb_per_kwh",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!F21"
      },
      "schema": {
        "type": "number"
      },
      "description": "Plant emission rate, active only for emissions_region_index=1 (Custom). Units: lb CO2/kWh. Omitted input retains publisher's source default 1.1.",
      "default": 1.1,
      "constraints": {
        "min": 0
      }
    },
    {
      "id": "transmission_loss_percent",
      "dir": "in",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!F26"
      },
      "schema": {
        "type": "number"
      },
      "description": "Transmission and distribution loss percentage; rate is divided by 1-loss/100. Units: percent points 0..10. Omitted input retains publisher's source default 5.",
      "default": 5,
      "constraints": {
        "min": 0,
        "max": 10
      }
    },
    {
      "id": "annual_energy_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!B18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Baseline total annual electricity use Units: kWh/year. Positive unless stated otherwise."
    },
    {
      "id": "annual_energy_savings_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!D18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Annual avoided electricity; excludes cooling and interactive effects Units: kWh/year. Positive unless stated otherwise."
    },
    {
      "id": "annual_cost_savings_usd",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!E18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Annual avoided electricity cost Units: USD/year. Positive unless stated otherwise."
    },
    {
      "id": "post_energy_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!F18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Annual electricity after selected actions Units: kWh/year. Positive unless stated otherwise."
    },
    {
      "id": "implementation_cost_usd",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!G18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Total implementation cost Units: USD. Positive unless stated otherwise."
    },
    {
      "id": "simple_payback_years",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!H18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Implementation cost divided by savings, source returns N/A for zero savings Units: years. Positive unless stated otherwise."
    },
    {
      "id": "annual_co2_savings_lb",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!I18"
      },
      "schema": {
        "type": "number"
      },
      "description": "Annual avoided CO2 with transmission-adjusted plant factor Units: lb CO2/year. Positive unless stated otherwise."
    },
    {
      "id": "effective_emissions_lb_per_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!F24"
      },
      "schema": {
        "type": "number"
      },
      "description": "Transmission-adjusted emissions rate Units: lb CO2/kWh. Positive unless stated otherwise."
    },
    {
      "id": "it_systems_savings_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!D16"
      },
      "schema": {
        "type": "number"
      },
      "description": "IT systems savings (includes UPS and other selected IT measures) Units: kWh/year. Positive unless stated otherwise."
    },
    {
      "id": "lighting_savings_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'Savings Summary'!D17"
      },
      "schema": {
        "type": "number"
      },
      "description": "Lighting electricity savings Units: kWh/year. Positive unless stated otherwise."
    },
    {
      "id": "power_chain_loss_kw",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!K26"
      },
      "schema": {
        "type": "number"
      },
      "description": "power chain loss kw Units: kW. Positive unless stated otherwise."
    },
    {
      "id": "transformer_efficiency",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!R18"
      },
      "schema": {
        "type": "number"
      },
      "description": "transformer efficiency Units: decimal fraction. Positive unless stated otherwise."
    },
    {
      "id": "ups_efficiency",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!R21"
      },
      "schema": {
        "type": "number"
      },
      "description": "ups efficiency Units: decimal fraction. Positive unless stated otherwise."
    },
    {
      "id": "pdu_efficiency",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!R24"
      },
      "schema": {
        "type": "number"
      },
      "description": "pdu efficiency Units: decimal fraction. Positive unless stated otherwise."
    },
    {
      "id": "ups_load_factor",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!Q21"
      },
      "schema": {
        "type": "number"
      },
      "description": "ups load factor Units: decimal fraction. Positive unless stated otherwise."
    },
    {
      "id": "current_pdu_load_factor",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!Q24"
      },
      "schema": {
        "type": "number"
      },
      "description": "current pdu load factor Units: decimal fraction. Positive unless stated otherwise."
    },
    {
      "id": "annual_power_chain_loss_kwh",
      "dir": "out",
      "shape": "scalar",
      "location": {
        "a1": "'User Inputs A'!L26"
      },
      "schema": {
        "type": "number"
      },
      "description": "annual power chain loss kwh Units: kWh/year. Positive unless stated otherwise."
    }
  ]
}