{"openapi":"3.1.0","info":{"title":"LBNL Electrical Power Chain Tool (v2.5)","version":"2.5.0","description":"LBNL Electrical Power Chain Tool with version-pinned publisher workbook calculations, scenario inputs and formula-level audit traces. selectCells reads at most 256 cells per request (including repeated cells). For licenseClass reference-only, cellOverrides, selectCells and trace may address only declared fio.yaml input/output port cells; trace traversal stops at that boundary. Verification level: scenario-independent-arithmetic.","x-formualizer-Provenance":{"publisher":"Lawrence Berkeley National Laboratory (LBNL — Center of Expertise for Energy Efficiency in Data Centers)","publisherPageUrl":"https://datacenters.lbl.gov/resources/electrical-power-chain-tool","sourceUrl":"https://datacenters.lbl.gov/sites/default/files/2023-07/Electrical%20Power%20Chain%20Tool%20v2.5%207-13-2023.xlsx","workbookFilename":"lbnl-power-chain-v2-5.xlsx","workbookSha256":"33a5f97e931ea540ef4bf6c09bf0cdc13cde0c93b5199d4ed23e15eae9c1b596","workbookBytes":176422,"format":"xlsx","licenseClass":"open-academic"},"x-formualizer-VerificationLevel":"scenario-independent-arithmetic","x-formualizer-WorkbookDownload":{"mode":"catalog-bytes","sourceUrl":"https://datacenters.lbl.gov/sites/default/files/2023-07/Electrical%20Power%20Chain%20Tool%20v2.5%207-13-2023.xlsx","sha256":"33a5f97e931ea540ef4bf6c09bf0cdc13cde0c93b5199d4ed23e15eae9c1b596","bytes":176422},"x-formualizer-Flows":[{"id":"quick_power_chain_savings","title":"Quick UPS and lighting savings","kind":"single","inputPorts":["ups_input_kw","ups_output_kw","it_equipment_kw","lighting_kw","electricity_cents_per_kwh","new_ups_load_factor","pursue_action_21","pursue_action_22","pursue_action_37","implementation_cost_18","implementation_cost_33","ups_savings_cap","lighting_savings_cap","custom_emissions_lb_per_kwh","transmission_loss_percent"],"outputPorts":["annual_energy_savings_kwh","annual_cost_savings_usd","post_energy_kwh","implementation_cost_usd","simple_payback_years","annual_co2_savings_lb"]},{"id":"full_power_chain_assessment","title":"Full electrical power-chain assessment","kind":"single","inputPorts":["transformer_input_kw","transformer_output_kw","transformer_capacity_kw","ups_input_kw","ups_output_kw","ups_capacity_kw","ups_claimed_efficiency","pdu_input_kw","pdu_output_kw","pdu_capacity_kw","generator_heater_kw","floor_area_sqft","it_equipment_kw","lighting_kw","electricity_cents_per_kwh","building_power_factor","building_thd","phase_balance","transformer_type","active_ups","ups_eco_mode","ups_old_capacitors","noncritical_power_source","pdu_transformer_type","pdu_load_factor","it_power_factor","rack_power_source","heater_power_source","heater_thermostat","lighting_design","lighting_control","lamp_type","pursue_action_16","pursue_action_17","pursue_action_18","pursue_action_19","pursue_action_20","pursue_action_21","pursue_action_22","pursue_action_23","pursue_action_24","pursue_action_25","pursue_action_26","pursue_action_27","pursue_action_28","pursue_action_29","pursue_action_30","pursue_action_31","pursue_action_32","pursue_action_33","pursue_action_34","pursue_action_35","pursue_action_36","pursue_action_37","pursue_action_38","pursue_action_39","pursue_action_40","new_ups_load_factor","new_pdu_load_factor","implementation_cost_14","implementation_cost_15","implementation_cost_16","implementation_cost_17","implementation_cost_18","implementation_cost_22","implementation_cost_23","implementation_cost_24","implementation_cost_25","implementation_cost_26","implementation_cost_27","implementation_cost_28","implementation_cost_29","implementation_cost_30","implementation_cost_31","implementation_cost_33","implementation_cost_36","ups_savings_cap","lighting_savings_cap","emissions_region_index","custom_emissions_lb_per_kwh","transmission_loss_percent"],"outputPorts":["annual_energy_kwh","annual_energy_savings_kwh","annual_cost_savings_usd","post_energy_kwh","implementation_cost_usd","simple_payback_years","annual_co2_savings_lb","effective_emissions_lb_per_kwh","it_systems_savings_kwh","lighting_savings_kwh","power_chain_loss_kw","transformer_efficiency","ups_efficiency","pdu_efficiency","ups_load_factor","current_pdu_load_factor","annual_power_chain_loss_kwh"]}]},"paths":{"/evaluate":{"post":{"operationId":"evaluateWorkbook","parameters":[{"name":"tablePort","in":"query","description":"Table input port receiving NDJSON rows or Arrow IPC; omit for scenario envelopes","schema":{"type":"string","enum":[]}},{"name":"flow","in":"query","description":"Named input/output flow (default: quick_power_chain_savings)","schema":{"type":"string","enum":["quick_power_chain_savings","full_power_chain_assessment"],"default":"quick_power_chain_savings"}}],"requestBody":{"required":true,"content":{"application/json":{"schema":{"type":"object","properties":{"inputs":{"$ref":"#/components/schemas/Inputs"}},"required":["inputs"]}},"application/x-ndjson":{"schema":{"type":"string","description":"Table rows with tablePort, otherwise scenario envelopes"}},"application/vnd.apache.arrow.stream":{"schema":{"type":"string","format":"binary"}},"application/octet-stream":{"schema":{"type":"string","format":"binary"}}}},"responses":{"200":{"description":"Workbook outputs","content":{"application/json":{"schema":{"type":"object","properties":{"outputs":{"$ref":"#/components/schemas/Outputs"}}}},"application/x-ndjson":{"schema":{"type":"string","description":"Scenario results, one JSON envelope per line"}}}}}}},"/evaluate-batch":{"post":{"operationId":"evaluateWorkbookBatch","requestBody":{"required":true,"content":{"application/json":{"schema":{"type":"object","properties":{"scenarios":{"type":"array","items":{"type":"object","properties":{"id":{},"inputs":{"$ref":"#/components/schemas/Inputs"}},"required":["inputs"]}}},"required":["scenarios"]}},"application/x-ndjson":{"schema":{"type":"string","description":"Scenario envelopes, one per line"}}}},"responses":{"200":{"description":"Scenario results (including per-scenario errors)","content":{"application/json":{"schema":{"type":"array","items":{"type":"object","properties":{"id":{},"outputs":{"$ref":"#/components/schemas/Outputs"},"error":{"type":"object","properties":{"message":{"type":"string"}},"required":["message"]}}}}},"application/x-ndjson":{"schema":{"type":"string"}}}}}}},"/ports":{"get":{"operationId":"describePorts","responses":{"200":{"description":"Workbook manifest and ports","content":{"application/json":{"schema":{"type":"object","properties":{"manifest":{"type":"object"},"ports":{"type":"array","items":{"type":"object"}}}}}}}}}},"/types.d.ts":{"get":{"operationId":"typeDeclarations","responses":{"200":{"description":"TypeScript Inputs, Outputs and Client declarations","content":{"text/plain":{"schema":{"type":"string"}}}}}}},"/v1/models/{slug}/{edition}/workbook.xlsx":{"get":{"summary":"Download catalog workbook or follow publisher redirect","description":"Download mode: catalog-bytes. Reference-only workbooks redirect to the publisher. The sha256 and bytes metadata pin the catalog file, which may be a sanitized derivative. When present, upstreamArtifact separately pins the publisher file. fio.yaml remains downloadable.","parameters":[{"name":"slug","in":"path","required":true,"schema":{"type":"string","enum":["lbnl-power-chain"]}},{"name":"edition","in":"path","required":true,"schema":{"type":"string","enum":["v2.5"]}}],"responses":{"200":{"description":"Catalog workbook bytes; upstreamArtifact separately identifies publisher bytes when sanitized","headers":{"x-workbook-sha256":{"schema":{"type":"string"},"description":"33a5f97e931ea540ef4bf6c09bf0cdc13cde0c93b5199d4ed23e15eae9c1b596"},"x-workbook-bytes":{"schema":{"type":"integer"},"description":"176422"}}}}}}},"components":{"schemas":{"Inputs":{"type":"object","properties":{"transformer_input_kw":{"type":"number","minimum":0,"description":"What is the annual average input power of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 650.","default":650},"transformer_output_kw":{"type":"number","minimum":0,"description":"What is the annual average output power of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 620.","default":620},"transformer_capacity_kw":{"type":"number","minimum":0,"description":"What is the nominal load capacity of the main IT transformer in kW? Units: kW. Omitted input retains publisher's source default 850.","default":850},"ups_input_kw":{"type":"number","minimum":0,"description":"What is the annual average input power of the UPS system in kW? Zero activates claimed-efficiency fallback; savings formulas still use measured input minus output, so supply measured input for retrofit analysis. Units: kW. Omitted input retains publisher's source default 580.","default":580},"ups_output_kw":{"type":"number","minimum":0,"description":"What is the annual average output power of the UPS system in kW? Units: kW. Omitted input retains publisher's source default 500.","default":500},"ups_capacity_kw":{"type":"number","minimum":0,"description":"What is the total load capacity of all active UPS modules in kW? Units: kW. Omitted input retains publisher's source default 750.","default":750},"ups_claimed_efficiency":{"type":"number","minimum":0,"maximum":1,"description":"What is the UPS manufacturer's claimed efficiency at the calculated load factor shown at right? Used only when ups_input_kw is zero. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.","default":0},"pdu_input_kw":{"type":"number","minimum":0,"description":"What is the annual average total PDU input power in kW? Units: kW. Omitted input retains publisher's source default 525.","default":525},"pdu_output_kw":{"type":"number","minimum":0,"description":"What is the annual average total PDU output power in kW? Units: kW. Omitted input retains publisher's source default 500.","default":500},"pdu_capacity_kw":{"type":"number","minimum":0,"description":"What is the total load capacity of all active PDUs in kW? Units: kW. Omitted input retains publisher's source default 600.","default":600},"generator_heater_kw":{"type":"number","minimum":0,"description":"What is the annual average backup generator engine block heater power demand in kW? Units: kW. Omitted input retains publisher's source default 10.","default":10},"floor_area_sqft":{"type":"number","minimum":0,"description":"What is the data center floor area in sq. ft.? Units: ft². Omitted input retains publisher's source default 10000.","default":10000},"it_equipment_kw":{"type":"number","minimum":0,"description":"What is the annual average IT equipment power demand in kW? Units: kW. Omitted input retains publisher's source default 515.","default":515},"lighting_kw":{"type":"number","minimum":0,"description":"What is the annual average lighting power demand in kW for the data center? Units: kW. Omitted input retains publisher's source default 20.","default":20},"electricity_cents_per_kwh":{"type":"number","minimum":0,"description":"What is the annual average unit cost of electricity in ¢/kWh? Units: cents/kWh. Omitted input retains publisher's source default 15.","default":15},"building_power_factor":{"type":"string","enum":["<0.9","≥0.9","Do not know."],"description":"What is the building power factor?  Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"building_thd":{"type":"string","enum":[">5%","≤5%","Do not know."],"description":"What is the building total harmonic current distortion (THD) at main feeder panel? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"phase_balance":{"type":"string","enum":["Out of balance by more than 10%.","Balanced to within 10% or less.","Do not know."],"description":"Are the loads balanced between all phases for the transformers, UPSs, and PDUs? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"transformer_type":{"type":"string","enum":["Temp rise ≥150 C and age >15 years old.","Temp rise ≥150 C and age ≤15 years old.","Temp rise < 150 C and age ≥ 15 years old.","Temp rise < 150 C and age < 15 years old.","N/A (no main IT transformer).","Do not know."],"description":"What is the age and type of the main transformer serving the IT power chain? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"active_ups":{"type":"string","enum":["Yes.","No.","Do not know."],"description":"Is there an active UPS? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Yes.\".","default":"Yes."},"ups_eco_mode":{"type":"string","enum":["Yes.","No.","N/A (No UPS, or no eco-mode capability).","Do not know."],"description":"Is the UPS operating in eco-mode? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"ups_old_capacitors":{"type":"string","enum":["Yes.","No.","Do not know.","N/A (no UPS)."],"description":"Are the UPS DC capacitors >5 years old? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"noncritical_power_source":{"type":"string","enum":["UPS.","Utility power.","Do not know."],"description":"What is the power source for non-critical loads? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"pdu_transformer_type":{"type":"string","enum":["Temp rise ≥150 C and age >15 years old.","Temp rise ≥150 C and age ≤15 years old.","Temp rise < 150 C and age ≥ 15 years old.","Temp rise < 150 C and age < 15 years old.","N/A (no transformers in PDUs).","Do not know."],"description":"What is the age and type of the transformers in the PDUs? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"pdu_load_factor":{"type":"string","enum":["<25%","≥25-50%",">50%","Do not know."],"description":"What is the average load factor for the active PDUs that contain transformers? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"it_power_factor":{"type":"string","enum":["<0.9","≥0.9","Do not know."],"description":"What is the IT equipment power factor? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"rack_power_source":{"type":"string","enum":["Alternating current (AC).","Direct current (DC).","Do not know."],"description":"What is the power source for the IT racks? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"heater_power_source":{"type":"string","enum":["Utility power.","Alternate power source, e.g. solar.","Do not know."],"description":"What is the power source for the emergency generator block heater(s)? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"heater_thermostat":{"type":"string","enum":["No.","Yes.","Do not know."],"description":"Does the block heater(s)/heater water jacket for emergency generator(s) operate with thermostat control? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"lighting_design":{"type":"string","enum":["No, the data center is over-lit and/or light is provided where it is not needed.","Yes, sufficient light is provided only to the areas that need it.","Do not know."],"description":"Is the data center lighting well-designed? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"lighting_control":{"type":"string","enum":["No control (always on).","Timeclock.","Manual Control.","Occupancy Sensor.","Do not know."],"description":"How are the lights controlled in the data center? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"No control (always on).\".","default":"No control (always on)."},"lamp_type":{"type":"string","enum":["Compact Fluorescent (CFL) or T12 Fluorescent.","T8 Fluorescent.","T5 Fluorescent.","LED.","Do not know."],"description":"What type of lamps are installed in the data center? Exact source option including punctuation; recommended actions require corresponding pursue_* selection. Units: source enum. Omitted input retains publisher's source default \"Do not know.\".","default":"Do not know."},"pursue_action_16":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 16; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_17":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 17; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_18":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 18; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_19":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 19; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_20":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 20; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".","default":"No"},"pursue_action_21":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 21; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".","default":"Yes"},"pursue_action_22":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 22; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".","default":"Yes"},"pursue_action_23":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 23; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".","default":"No"},"pursue_action_24":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 24; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_25":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 25; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_26":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 26; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_27":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 27; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_28":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 28; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_29":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 29; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_30":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 30; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_31":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 31; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_32":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 32; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_33":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 33; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_34":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 34; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_35":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 35; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".","default":"No"},"pursue_action_36":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 36; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"No\".","default":"No"},"pursue_action_37":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 37; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"Yes\".","default":"Yes"},"pursue_action_38":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 38; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_39":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 39; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"pursue_action_40":{"type":"string","enum":["Yes","No","N/A"],"description":"Pursue displayed action at row 40; requires a compatible question response. Yes selects it, No declines it, N/A means unavailable. Rows 21/22 are modular/right-size UPS; 37 is occupancy lighting. Units: source enum. Omitted input retains publisher's source default \"N/A\".","default":"N/A"},"new_ups_load_factor":{"type":"number","enum":[0.1,0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1],"description":"Post-retrofit UPS load fraction. Active if any UPS row 20–23 action is pursued; exact tenth-step lookup, no interpolation. Units: decimal fraction. Omitted input retains publisher's source default 0.8.","default":0.8},"new_pdu_load_factor":{"type":"string","enum":["<25%","≥25-50%",">50%"],"description":"Post-action PDU loading; active with PDU rightsizing action. Units: source enum. Omitted input retains publisher's source default \">50%\".","default":">50%"},"implementation_cost_14":{"type":"number","minimum":0,"description":"Estimated cost for action group row 14. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_15":{"type":"number","minimum":0,"description":"Estimated cost for action group row 15. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_16":{"type":"number","minimum":0,"description":"Estimated cost for action group row 16. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_17":{"type":"number","minimum":0,"description":"Estimated cost for action group row 17. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_18":{"type":"number","minimum":0,"description":"Estimated cost for action group row 18. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 300000.","default":300000},"implementation_cost_22":{"type":"number","minimum":0,"description":"Estimated cost for action group row 22. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_23":{"type":"number","minimum":0,"description":"Estimated cost for action group row 23. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_24":{"type":"number","minimum":0,"description":"Estimated cost for action group row 24. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_25":{"type":"number","minimum":0,"description":"Estimated cost for action group row 25. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_26":{"type":"number","minimum":0,"description":"Estimated cost for action group row 26. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_27":{"type":"number","minimum":0,"description":"Estimated cost for action group row 27. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_28":{"type":"number","minimum":0,"description":"Estimated cost for action group row 28. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_29":{"type":"number","minimum":0,"description":"Estimated cost for action group row 29. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_30":{"type":"number","minimum":0,"description":"Estimated cost for action group row 30. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_31":{"type":"number","minimum":0,"description":"Estimated cost for action group row 31. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"implementation_cost_33":{"type":"number","minimum":0,"description":"Estimated cost for action group row 33. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 15000.","default":15000},"implementation_cost_36":{"type":"number","minimum":0,"description":"Estimated cost for action group row 36. Cost is counted by source even if pursuit is disabled; set cost to zero when cancelling an action. Rows 18 and 33 are UPS and lighting-control projects. Units: USD. Omitted input retains publisher's source default 0.","default":0},"ups_savings_cap":{"type":"number","minimum":0,"maximum":1,"description":"Maximum combined savings fraction of UPS losses; source omits interactive effects. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.8.","default":0.8},"lighting_savings_cap":{"type":"number","minimum":0,"maximum":1,"description":"Maximum combined savings fraction of lighting consumption. Units: decimal fraction 0..1. Omitted input retains publisher's source default 0.8.","default":0.8},"emissions_region_index":{"type":"number","enum":[1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31,32,33,34,35,36,37,38,39,40,41,42,43,44,45,46,47,48,49,50,51],"description":"Source list-box linked row: 1=Custom, 2..51 follows P11:P60 state abbreviations. The visible F20 text is not the formula selector. State map: 1=Custom, 2=AL, 3=AK, 4=AZ, 5=AR, 6=CA, 7=CO, 8=CT, 9=DE, 10=FL, 11=GA, 12=HI, 13=ID, 14=IL, 15=IN, 16=IA, 17=KS, 18=KY, 19=LA, 20=ME, 21=MD, 22=MA, 23=MI, 24=MN, 25=MS, 26=MO, 27=MT, 28=NE, 29=NV, 30=NH, 31=NJ, 32=NM, 33=NY, 34=NC, 35=ND, 36=OH, 37=OK, 38=OR, 39=PA, 40=RI, 41=SC, 42=SD, 43=TN, 44=TX, 45=UT, 46=VT, 47=VA, 48=WA, 49=WV, 50=WI, 51=WY Units: integer lookup index. Omitted input retains publisher's source default 1.","default":1},"custom_emissions_lb_per_kwh":{"type":"number","minimum":0,"description":"Plant emission rate, active only for emissions_region_index=1 (Custom). Units: lb CO2/kWh. Omitted input retains publisher's source default 1.1.","default":1.1},"transmission_loss_percent":{"type":"number","minimum":0,"maximum":10,"description":"Transmission and distribution loss percentage; rate is divided by 1-loss/100. Units: percent points 0..10. Omitted input retains publisher's source default 5.","default":5}},"required":[],"additionalProperties":false},"Outputs":{"type":"object","properties":{"annual_energy_kwh":{"type":"number","description":"Baseline total annual electricity use Units: kWh/year. Positive unless stated otherwise."},"annual_energy_savings_kwh":{"type":"number","description":"Annual avoided electricity; excludes cooling and interactive effects Units: kWh/year. Positive unless stated otherwise."},"annual_cost_savings_usd":{"type":"number","description":"Annual avoided electricity cost Units: USD/year. Positive unless stated otherwise."},"post_energy_kwh":{"type":"number","description":"Annual electricity after selected actions Units: kWh/year. Positive unless stated otherwise."},"implementation_cost_usd":{"type":"number","description":"Total implementation cost Units: USD. Positive unless stated otherwise."},"simple_payback_years":{"type":"number","description":"Implementation cost divided by savings, source returns N/A for zero savings Units: years. Positive unless stated otherwise."},"annual_co2_savings_lb":{"type":"number","description":"Annual avoided CO2 with transmission-adjusted plant factor Units: lb CO2/year. Positive unless stated otherwise."},"effective_emissions_lb_per_kwh":{"type":"number","description":"Transmission-adjusted emissions rate Units: lb CO2/kWh. Positive unless stated otherwise."},"it_systems_savings_kwh":{"type":"number","description":"IT systems savings (includes UPS and other selected IT measures) Units: kWh/year. Positive unless stated otherwise."},"lighting_savings_kwh":{"type":"number","description":"Lighting electricity savings Units: kWh/year. Positive unless stated otherwise."},"power_chain_loss_kw":{"type":"number","description":"power chain loss kw Units: kW. Positive unless stated otherwise."},"transformer_efficiency":{"type":"number","description":"transformer efficiency Units: decimal fraction. Positive unless stated otherwise."},"ups_efficiency":{"type":"number","description":"ups efficiency Units: decimal fraction. Positive unless stated otherwise."},"pdu_efficiency":{"type":"number","description":"pdu efficiency Units: decimal fraction. Positive unless stated otherwise."},"ups_load_factor":{"type":"number","description":"ups load factor Units: decimal fraction. Positive unless stated otherwise."},"current_pdu_load_factor":{"type":"number","description":"current pdu load factor Units: decimal fraction. Positive unless stated otherwise."},"annual_power_chain_loss_kwh":{"type":"number","description":"annual power chain loss kwh Units: kWh/year. Positive unless stated otherwise."}},"required":["annual_energy_kwh","annual_energy_savings_kwh","annual_cost_savings_usd","post_energy_kwh","implementation_cost_usd","simple_payback_years","annual_co2_savings_lb","effective_emissions_lb_per_kwh","it_systems_savings_kwh","lighting_savings_kwh","power_chain_loss_kw","transformer_efficiency","ups_efficiency","pdu_efficiency","ups_load_factor","current_pdu_load_factor","annual_power_chain_loss_kwh"],"additionalProperties":false}}}}